20KV Level S13-M Series Of Three-Phase Double-Winding Distribution Transformer With Off-Circuit Tap-Changer

● 20kv Ievel S13-M series of three-phase double-windinq distribution transformer with off-circuit tap-changer is using the type of S11-M serial full-sealed oiI-immersed type transformer it has nol oiI conservator moisture absorber and other devices. Coil is using Iayer-to-layer structure, ampere-turns evenly distributed, the insulation structure is reasonable and has a strong short circuit impact resistance Using the ripple fuel tank, wave wings can follow with the dilatation of transformer oil while dilatation, thereby make transformer internal maintain a certain pressure, enhance the reliability of the operational.

● Apply to power plant(station), substation(power distribution station) and industrial, business, building etc.

● Implement GB1094, GB6451 national standards etc.

    Rated capacity (KV A) Voltage Combination (kv) Connection symbol NO-load loss (KW) Full-load loss (KW) NO-load cu rent (%) Impedance (%) Weight(kg) Outline Dimension(mm) Gauge ( mm)
    HV LV Oil Weight Total Weight L W H
    30 20
    ±5%
    OR 
    ±2
    x2.5%
    0.4 Dyn11
    Yyn0
    80 690/660 2.1 5.5 100 360 800 680 950 400 x 400
    50 104 1010/960 2 120 410 850 700 970 400 x 400
    63 120 1200/1150 1.9 140 480 880 710 1000 400 x 400
    80 144 1440/1370 1.8 150 540 900 720 1030 400 x 400
    100 160 1730/1650 1.6 170 615 950 750 1050 400 x 400
    125 192 2080/1980 1.5 180 710 950 900 1070 550 x 550
    160 232 2540/2420 1.4 195 790 1000 900 1100 550 x 550
    200 272 3000/2860 1.3 220 910 1050 930 1120 550 x 550
    250 320 3520/3350 1.2 245 1040 1100 950 1150 550 x 550
    315 384 4210/4010 1.1 280 1185 1450 950 1200 550 x 550
    400 456 4970/4730 1 300 1370 1500 1000 1250 660 x 660
    500 544 5940/5660 1 350 1620 1550 1050 1320 660 x 660
    630 648 6820 0.9 6 420 2085 1650 1100 1350 660 x 660
    800 784 8250 0.8 465 2400 1700 1200 1450 820 x 820
    1000 920 11330 0.7 580 2880 1900 1350 1500 820 x 820
    1250 1100 13200 0.7 640 3300 1950 1380 1550 820 x 820
    1600 1330 15950 0.6 770 4000 2050 1450 1600 820 x 820

    Note:

    1. For transformers with the capacity of 500 kVA and below, above the diagonal values of loss of load application Dyn11 connection g roup, below the diagonal load loss value applicable to Yyn0 connected node.

    2. The loss parameter in the table is also suitable for high voltage dual voltage 20(10) of the three-phase transformer.

    Please feel cost-free to send us your specifications and we'll respond to you asap. We've got a professional engineering team to serve for the every single detailed needs.So that you can meet your desires, please really feel cost-free to contact us. You could send us emails and call us straight. Additionally, we welcome visits to our factory from all over the world for much better recognizing of our corporation. and merchandise. In our trade with merchants of several countries, we often adhere to the principle of equality and mutual advantage. It is our hope to market, by joint efforts, both trade and friendship to our mutual benefit. We look forward to getting your inquiries. 