20KV Level S13-M Series Of Three-Phase Double-Winding Distribution Transformer With Off-Circuit Tap-Changer
| Rated capacity (KV A) | Voltage Combination (kv) | Connection symbol | NO-load loss (KW) | Full-load loss (KW) | NO-load cu rent (%) | Impedance (%) | Weight(kg) | Outline Dimension(mm) | Gauge ( mm) | ||||
| HV | LV | Oil Weight | Total Weight | L | W | H | |||||||
| 30 | 20
±5% OR ±2 x2.5% |
0.4 | Dyn11 Yyn0 |
80 | 690/660 | 2.1 | 5.5 | 100 | 360 | 800 | 680 | 950 | 400 x 400 |
| 50 | 104 | 1010/960 | 2 | 120 | 410 | 850 | 700 | 970 | 400 x 400 | ||||
| 63 | 120 | 1200/1150 | 1.9 | 140 | 480 | 880 | 710 | 1000 | 400 x 400 | ||||
| 80 | 144 | 1440/1370 | 1.8 | 150 | 540 | 900 | 720 | 1030 | 400 x 400 | ||||
| 100 | 160 | 1730/1650 | 1.6 | 170 | 615 | 950 | 750 | 1050 | 400 x 400 | ||||
| 125 | 192 | 2080/1980 | 1.5 | 180 | 710 | 950 | 900 | 1070 | 550 x 550 | ||||
| 160 | 232 | 2540/2420 | 1.4 | 195 | 790 | 1000 | 900 | 1100 | 550 x 550 | ||||
| 200 | 272 | 3000/2860 | 1.3 | 220 | 910 | 1050 | 930 | 1120 | 550 x 550 | ||||
| 250 | 320 | 3520/3350 | 1.2 | 245 | 1040 | 1100 | 950 | 1150 | 550 x 550 | ||||
| 315 | 384 | 4210/4010 | 1.1 | 280 | 1185 | 1450 | 950 | 1200 | 550 x 550 | ||||
| 400 | 456 | 4970/4730 | 1 | 300 | 1370 | 1500 | 1000 | 1250 | 660 x 660 | ||||
| 500 | 544 | 5940/5660 | 1 | 350 | 1620 | 1550 | 1050 | 1320 | 660 x 660 | ||||
| 630 | 648 | 6820 | 0.9 | 6 | 420 | 2085 | 1650 | 1100 | 1350 | 660 x 660 | |||
| 800 | 784 | 8250 | 0.8 | 465 | 2400 | 1700 | 1200 | 1450 | 820 x 820 | ||||
| 1000 | 920 | 11330 | 0.7 | 580 | 2880 | 1900 | 1350 | 1500 | 820 x 820 | ||||
| 1250 | 1100 | 13200 | 0.7 | 640 | 3300 | 1950 | 1380 | 1550 | 820 x 820 | ||||
| 1600 | 1330 | 15950 | 0.6 | 770 | 4000 | 2050 | 1450 | 1600 | 820 x 820 | ||||
Note:
1. For transformers with the capacity of 500 kVA and below, above the diagonal values of loss of load application Dyn11 connection g roup, below the diagonal load loss value applicable to Yyn0 connected node.
2. The loss parameter in the table is also suitable for high voltage dual voltage 20(10) of the three-phase transformer.
Please feel cost-free to send us your specifications and we'll respond to you asap. We've got a professional engineering team to serve for the every single detailed needs.So that you can meet your desires, please really feel cost-free to contact us. You could send us emails and call us straight. Additionally, we welcome visits to our factory from all over the world for much better recognizing of our corporation. and merchandise. In our trade with merchants of several countries, we often adhere to the principle of equality and mutual advantage. It is our hope to market, by joint efforts, both trade and friendship to our mutual benefit. We look forward to getting your inquiries.