MLS-V Low Voltage Switchgear Of Drawer Model
| Project Name | Technical parameter | |
| Rated operational Voltage (V) | Main Circuit | ≤AC 400V |
| Auxiliary Circuit | ≤AC 380V , ≤DC 220V | |
| Rated Insulation Voltage (V) | Main Circuit | AC 690V |
| Rated Impulse Withstand Voltage (1 .2/50 us ) kV | Main Circuit | 6 、8 |
| Rated Operating Current (IP4Xtime) * A | Main Bus-bar | ≤5000、≤3600 (MLS Double side cabinet) |
| Vertical Bus | 790 1000 1250 1600 (Draw out type),≤2500 (Plug in type MCCB) | |
| Rated Short Time withstand Current kA/1s | Vertical Bus | 50 、 65 、 80 、 100 |
| Main Bus-bar | 50 、 65 、 80 、 90 | |
| Rated Peak-value Withstand Current kA/0 .1 s | Main Bus-bar | 105 、143 、176 、220 |
| Vertical Bus | 105 、143 、176 、198 | |
Whan the protection grade is IP55, the main busbar rated working current is less than 2500A.